Thermal Grease Kit
Instructions
The thermal bond between the processor heat sink and the processor requires thermal grease
for proper operation. Every time you remove or replace the processor heat sink, you must replace
the thermal grease on the processor below the heat sink. New grease and alcohol wipes for
cleaning o the old grease are included with certain replacement parts and in a separate thermal
grease kit. Instructions for applying the grease are provided in this procedure.
Follow the instructions in this document carefully. Failure to follow these instructions could
damage your equipment and void its warranty.
Note: Online instructions are available at http://www.apple.com/support/diy/.
Kit Contents
The following are included in the thermal grease kit:
2 syringes of pre-measured thermal grease
2 alcohol wipes for cleaning previous thermal grease o processors and heat sinks
Working Safely Inside the Xserve
Always touch the Xserve enclosure to discharge static electricity before you touch any
components inside the Xserve. To avoid generating static electricity, do not walk around the
room until you have nished working inside the server and have replaced the cover. To minimize
the possibility of damage due to static discharge, wear an antistatic wrist strap while you work
inside the Xserve.
Warning: Always shut down the Xserve, and disconnect the power cords before opening
it to avoid damaging its internal components or the components you are installing. Don’t
open the server while it is turned on. Even after you shut down the Xserve, its internal
components can be very hot. Let it cool before you open it.
Przeglądanie stron 0
1 2 3 4 5 6 ... 13 14

Podsumowanie treści

Strona 1 - Thermal Grease Kit

 Xserve (Late 2006/Early 2008)073-1108 Rev. BThermal Grease KitInstructionsThe thermal bond between the processor heat sink and the processor require

Strona 2 - Thumbscrews

Xserve (Late 2006/Early 2008) Thermal Grease Kit Instructions 10Holding the processor by three corners only, keep the processor level as you place it

Strona 3 - Opening the Xserve

Xserve (Late 2006/Early 2008) Thermal Grease Kit Instructions 11Note: When installing the processor on the logic board, align the processor notch wit

Strona 4 - Processor Heat Sink

Xserve (Late 2006/Early 2008) Thermal Grease Kit Instructions 12Replacing the Processor Heat SinksImportant: Before re-installing each heat sink, be

Strona 5

Xserve (Late 2006/Early 2008) Thermal Grease Kit Instructions 13Replacing the Airow DuctLower the airow duct into position on the logic board. 1. N

Strona 6

Xserve (Late 2006/Early 2008) Thermal Grease Kit Instructions 14Closing the XserveReplace and secure the cover.1. Slide the Xserve back into the rack

Strona 7 - Using the Thermal Grease Kit

Xserve (Late 2006/Early 2008) Thermal Grease Kit Instructions 2Removing the Xserve from a RackAlert users that the server will be unavailable for a p

Strona 8

Xserve (Late 2006/Early 2008) Thermal Grease Kit Instructions 3Opening the XserveLoosen the thumbscrews at the back of the top cover and slide the co

Strona 9

Xserve (Late 2006/Early 2008) Thermal Grease Kit Instructions 4 Processor Heat SinkNote: Server congurations with a single processor have a regular

Strona 10

Xserve (Late 2006/Early 2008) Thermal Grease Kit Instructions 5Loosen the four screws securing the heat sink in the order indicated below. 1.

Strona 11

Xserve (Late 2006/Early 2008) Thermal Grease Kit Instructions 6Caution: Whenever you handle the heat sink, handle it from the slotted sides, not the

Strona 12

Xserve (Late 2006/Early 2008) Thermal Grease Kit Instructions 7Caution: Each heat sink is connected to the logic board by a small 2-pin thermal senso

Strona 13 - Replacing the Airow Duct

Xserve (Late 2006/Early 2008) Thermal Grease Kit Instructions 8Carefully lift the processor out of the holder. 3. Important: When removing or install

Strona 14 - Closing the Xserve

Xserve (Late 2006/Early 2008) Thermal Grease Kit Instructions 9Using the syringe of thermal grease that came with the replacement processor, apply th